About Batteries

                        

Home Benefits Specs & Prices FAQ Warranty Installation Diagrams MSDS Sheets Maintenance About Batteries Down Loads

Contact Us

Voice: 941-474-0110

Fax: 941-474-1983

1-800-718-8816

9am-4pm Eastern

Technical rob@nwes.com

Sales: jean@nwes.com

 

This information does not apply to any VRLA, AGM, or Gelled, type batteries

Freezing Points of Battery Electrolyte

Specific Gravity Centigrade Fahrenheit
1.000 0 +32
1.050 -3.3 +25
1.100 -7.7 +18
1.125 -10 +18
1.150 -15 +5
1.175 -20 -4
1.200 -26 -15
1.210 -31 -23
1.220 -36 -33
1.230 -41 -42
1.260 -57 -71
1.270 -62 -80
1.280 -66 -87
1.290 -69 -92

 

Temperature Effects on Voltage

Electrolyte Temperature °F Cell Voltage to be subtracted from measured volts Electrolyte Temperature °F Cell Voltage to be added to measured volts
49-51 -.09 76-78 None Needed
52-42 -.08 79-81 +.01
55-57 -.07 82-84 +.02
58-60 -.06 85-87 +.03
61-63 -.05 88-90 +.04
64-66 -.04 91-93 +.05
67-69 -.03 94-96 +.06
70-72 -.02 97-99 +.07
73-75 -.01 100-102 +.08

 

Temperature Effects on Capacity

Electrolyte Temperature °F Percent Capacity
77 100%
60 95%
50 91%
40 87%
30 81%

 

Temperature Effects On Specific Gravity

Electrolyte Temperature °F Correction Factor
39-41 -.012
42-44 -.011
45-47 -.010
48-50 -.009
51-53 -.008
54-56 -.007
57-60 -.006
61-63 -.005
64-66 -.004
67-69 -.003
70-72 -.002
73-75 -.001
76-78 0.00 No Change
79-81 +.001
82-84 +.002
85-87 +.003
88-91 +.004
92-94 +.005

 

The graph below pertains to batteries that have a fully charged Specific Gravity of 1.280. Graphs for other batteries will appear different.

 

Contact Us

 Voice:941-474-0110  9am-4pm Eastern Time

Copyright © 2006/2008 Northwest Energy Storage   Solar-One® is a registered Trade Mark of Northwest Energy Storage
HuP® is a registered trade mark of EnerSys®
Last modified: September 24, 2008

Contact the Webmaster